Type 47 Differential Pressure Sustaining Valve

Type 47 Differential Pressure Sustaining Valve

Features

  • Accurate differential pressure control


  • Reliable &excellent sealing


  • Reliable fully-liquid pressure control


  • Larger flow rate


  • Completely automatic operation

Features

  • Accurate differential pressure control


  • Reliable &excellent sealing


  • Reliable fully-liquid pressure control


  • Larger flow rate


  • Completely automatic operation

Type 47 Differential Pressure Sustaining Valve

Model 47-09 differential pressure sustaining valve is a fully automatic and liquid-pressure control valve. Using the pressure difference between two pipes controls the pressure difference not to over the acceptable range of the system during valve operation or flow rate variety. The valve will automatically open when pressure difference is increased, and will automatically close when pressure difference is decreased. So that it can maintain the pressure difference between two pipes.


Schematic Diagram

 

 

Accessories

   No. Parts Name
    1

Strainer

    2

Needle valve / Ball valve

    3

Ball valve

    4

Pilot

     5

Basic valve body


Dimension
 

 

 

Valve size

50

65

80

100

125

L (mm)

200

220

285

307

370

H (mm)

87 109 115 137

142

Weight (kg)

7

9

16

18

37

           

Valve size

150

200

250

300

 

L (mm)

390

500

605

650

 

H (mm)

164 183 244 258  

Weight (kg)

48

83

120

140

 

 

Notice:

※When installing the valve, strongly request to leave enough space for maintenance. It is necessary to install the filter at the front section of the valve to avoid foreign materials to block the valve and affect the operation of the valve.

※King-Tech reserves the right to make any revisions on the valve model and size without prior notification.

※When making any design drawing, installation drawing or construction drawing, please do get our approved CAD with our signature, or we will not be responsible for any mistake.


Specification

Size:DN50~DN300 to flange

Flange:10K、16K、PN16、150LB

Temp. range:0℃~100℃,water

※Any size over DN350 can be made to order.


Material

Body:Iron casting / Stainless steel

Accessory:Brass / Stainless steel

Fastener:Carbon steel / Stainless steelDiaphragm:NBR / EPDM


Pilot Specification

Adjustable pressure range:0.1~4 bar、3~9 bar

Temp. range:0℃~100℃,water

Material:Brass / Stainless steel


When Ordering, Please Specify

1、Valve model number

2、Valve size

3、Pressure range

4、Connection type

5、Other optional parts

6、Working pressure


Typical Application

 

 

Protection pump

47-09 differential pressure sustaining valve can maintain the pressure difference of the flow through the pump either the water supply at the upstream or the variety requirement at the downstream. It can steadily maintain and control stable pressure difference at both sides of the pump. So that it can control the flow rate to prevent the damage caused by overload or air etching when the pump is over demanded. 
 
 
 
 
 
 
Bypass

47-09 differential pressure sustaining valve can be used in the circular system to ensure the pressure difference between the supply pipe and the back-flow pipe. In the filter system (bypass), the pressure difference will enlarge when the filter is blocked. By using a model 47-09, the valve will open to compensate the flow rate at the after end to avoid damaging the system.